Recloser

Electricity distribution networks circuit breakers

  • 8 min read
  • 8 chapters

Related on Lably

Through Electrical engineering, Transformer and Hydraulics

For overhead electric power distribution networks, up to 80-87% of faults are transient. Transient faults can occur due to various causes, such as lightning strikes, voltage surges, or foreign objects coming into contact with exposed distribution lines. When a transient fault occurs, the resulting arc will ionize the air. The ionized air will maintain the arc even after the material that caused the short circuit is removed. Consequently, these transient faults can be resolved by a simple reclose operation. The minimum reclose time allowed for any operation is .3 seconds. This is the minimum amount of time required for the ionization to dissipate from the arc path. Reclosers are designed to handle a rapid open-close duty cycle, where electrical engineers can optionally configure the number and timing of attempted close operations prior to transitioning to a lockout stage. The number of reclose attempts is limited to a maximum of four by recloser standards noted above.

At two multiples of the rated current, the recloser's rapid trip curve can cause a trip (off circuit) in as little as 1.5 cycles (or 30 milliseconds). During those 1.5 cycles, other separate circuits can see voltage dips or blinks until the affected circuit opens to stop the fault current. Automatically closing the breaker after it has tripped and stayed open for a brief amount of time, usually after 1 to 5 seconds, is a standard procedure.

Reclosers are often used as a key component in a smart grid, as they are effectively computer controlled switchgear which can be remotely operated and interrogated using supervisory control and data acquisition (SCADA) or other communications. Interrogation and remote operation capabilities allow utilities to aggregate data about their network performance, and develop automation schemes for power restoration. Automation schemes can either be distributed (executed at the remote recloser level) or centralized (close and open commands issued by a central utility control room to be executed by remotely controlled closes).

Description

Reclosers are made in single-phase and three-phase versions, using oil, vacuum, or sulfur hexafluoride (SF6) interrupters. Controls for the reclosers range from the original electromechanical systems to digital electronics with metering and SCADA functions. The ratings of reclosers run from 2.4–38 kV for load currents from 10–1200 A and fault currents from 1–16 kA.

On a 3-phase circuit, a recloser is more beneficial than three separate fuse cutouts. For example, on a wye to delta conversion, when cutouts are used on the wye side and only 1 out of 3 of the cutout fuses open, some customers on the delta side have a low voltage condition, due to voltage transfer through the transformer windings. Low voltage can cause severe damage to electronic equipment. But when a recloser is used, all three phases open, thereby eliminating the problem.