Electrical wiring in the United Kingdom

  • 39 min read
  • 10 chapters

Related on Lably

Through United Kingdom, Voltage and Alternating current

Installations are distinguished by a number of criteria, such as voltage (high, low, extra low), phase (single or three-phase), nature of electrical signal (power, data), type and design of cable (conductors and insulators used, cable design, solid/fixed or stranded/flexible, intended use, protective materials), circuit design (ring, radial), and so on.

Electrical wiring is ultimately regulated to ensure safety of operation, by such as the building regulations, currently legislated as the Building Regulations 2010, which lists "controlled services" such as electric wiring that must follow specific directions and standards, and the Electricity at Work Regulations 1989. The detailed rules for end-use wiring followed for practical purposes are those of BS 7671 Requirements for Electrical Installations. (IET Wiring Regulations), currently in its 18th edition, which provide the detailed descriptions referred to by legislation.

UK electrical wiring standards are largely harmonised with the regulations in other European countries and the international IEC 60446 standard. However, there are a number of specific national practices, habits and traditions that differ significantly from other countries, and which in some cases survived harmonisation. These include the use of ring circuits for domestic and light commercial fixed wiring, fused plugs, and for circuits installed prior to harmonisation, historically unique wiring colours.

Common terminology

Regulatory

BS 7671 "Requirements for Electrical Installations. IET Wiring Regulations" (the regs, or wiring regs)
These are detailed rules for the design, installation and sign-off for end-user electrical installations. Compliance with BS 7671 is not mandatory, but official guidance states following BS 7671 is one way to demonstrate compliance with the building regulations.
xxth edition
Reference to a specific edition of the BS 7671 regulations.
Building regulations – "Part P"
Section of the Building Regulations for England and Wales addressing electrical wiring and safety in residential situations and outbuildings.
Local authority building control (LABC; building control)
Local council department responsible for overseeing and administering building regulations.
Competent person scheme
Private organizations authorised by the state to supervise, accredit, and control the registration of installers, who, as members of this scheme, may self-certify that any domestic work classed as notifiable to a LABC that they have undertaken, is compliant with building regulations, thus avoiding inspection by LABC (or by a member of the third-party certifier scheme).
Minor electrical installation works certificate (MEIWC)
Formal certificate for confirming that minor work items, such as the addition of a new socket or light to an existing circuit, have been designed, constructed, inspected and tested in accordance with BS 7671.
Electrical installation certificate (EIC)
Formal certificate for confirming that a major piece of work, such as a completely new installation; complete rewire; addition of a whole new circuit; or replacement of a consumer unit, has been designed, constructed, inspected and tested in accordance with BS 7671.
Electrical installation condition report (EICR, ICR); previously the periodic inspection report (PIR)
Formal report of the condition of an existing wiring installation.
Permit to work
Formal confirmation that electrical wiring is isolated and fully made safe, prior to working on it, required prior to any high voltage works and other high risk activities.
Skilled Person (electrically); (formally "Competent Person")
Defined by BS 7671 as "Person who possesses, as appropriate to the nature of the electrical work to be undertaken, adequate education, training and practical skills, and who is able to perceive risks and avoid hazards which electricity can create". The Electricity at Work Regulations requires persons to be competent to prevent danger and injury.

Distribution within premises

Consumer unit, consumer control unit, or consumer distribution unit (CU, CDU, CCU; historically and commonly, fuse board/box)
Distribution board designed for ordinary low voltage single phase premises, primarily domestic and light commercial wiring. 3-phase power distribution boards are usually known as distribution boards.
Distribution board (DB)
Panel that splits power from one main source into separate circuits, each with independent protection.

Breakers and safety devices

Fuse
An overcurrent protection device. Prior to the invention of the resettable circuit breaker, distribution boards (then called fuseboxes) held fuses to protect individual circuits. The fuses used in fuseboxes were either of the cartridge type, similar to those found in UK plugs, or replaceable fuse-wire held within two-prong enclosures. Other standard use of fuses include those within appliance plugs, and the main fuse located on the end of the service (supply) cable (at the service head).
Breaker (circuit breaker, CB)
Any fixed device that breaks a circuit (that is, while it is drawing current) upon fault condition detection. Unlike a fuse, a circuit breaker can be reset by flipping a switch.
Miniature circuit breaker (MCB)
An overcurrent protection circuit breaker. These have standardised current ratings and tripping characteristics, and can be installed in close proximity in consumer units and distribution boards.
Residual-current device (RCD), also residual current circuit breaker (RCCB)
A circuit breaker triggered by unequal currents in line and neutral wires (i.e., electrical power is passing to earth). Mandatory for most circuits as of 17th Edition regulations.
Residual current circuit breaker with overcurrent protection (RCBO)
Combination of RCD and MCB; breaks circuit on being triggered either as an RCD or by overcurrent.
Surge protection device (SPD)
A transient overcurrent or overvoltage protection device; safely diverts away very short-lived spikes of current or voltage. Type 1 devices provide protection from direct lightning strikes to vulnerable structures (those having a conductive structure, a lightning rod, or an overhead power supply). These should always be used in combination with type 2. Type 2 devices protect against indirect strikes. Type 3 devices are supplementary to type 2, installed near sensitive equipment.
Arc fault detection device (AFDD)
A circuit breaker triggered by detection of an electric arc; breaks circuit on detecting an electric arc, which could develop from the likes of loose wires.
Earth leakage circuit breaker (ELCB)
An obsolete circuit breaker triggered by voltage on the earth wiring. This was a precursor to the RCD, with disadvantages of covering fewer fault scenarios, and potentially not working at all in the presence of parallel earth paths (e.g. bonding of gas/water pipes).
Isolator switch (or isolator)
Used for isolating a device from its power supply for maintenance or safety reasons. These are commonly being fitted in recent years, alongside fitting of new electricity meters, for the benefit of enabling electricians to replace consumer units without the hassle of arranging for the DNO to temporarily isolate the supply by removing the supply's main fuse (or taking on the potential danger and legal risks of doing so themself). There is a very important difference to be aware of between a device categorised as a switch vs. an isolator, and these devices may commonly be referred to as isolator/isolation switches when they may not actually be rated as anything more than isolators. A switch is a device capable of safely disconnecting the supply even if devices in the installation were drawing the full maximum load the installation was rated for. An isolator is not, it should only be used when the installation is drawing no power, i.e. the main switch in the consumer unit is off. When a supply is switched off under load, some degree of electrical arcing takes place across the contacts. A switch is designed to safely handle this. An isolator is not and could become weakened or instantly fail in a dangerous way, depending upon the size of the load. Utilising an isolator incorrectly as a switch is thus a significant hazard and this danger may well be unintuitive for many.

Wires and cables (conductors)

Live
A power-carrying conductor. This term is commonly used incorrectly by the general public in place of line, owing to changes to standard definitions since the 1980s. By definition it applies to any conductor that is intended to be energised during normal use, including a neutral conductor, but not by convention a PEN conductor. I.e line and neutral are live conductors, but earth is not.
Line (L; or phase line)
A power-carrying conductor in a typical low-voltage or domestic installation. Colour-coded brown (pre-2004: red).
Neutral (N)
A power-carrying conductor in a typical low-voltage or domestic installation, usually bonded to Earth (ground) voltage by the supplier. Colour-coded blue (pre-2004: black).
Earth (E; or protective earth (PE), or circuit protective conductor (CPC))
A conductor that provides a connection to Earth for safety and protection purposes, for both end-user devices and metal objects and components in the installation. Colour-coded green/yellow striped, though may be bare (uninsulated) within sheathed cable (pre-1976: solid green).
Conduit
A form of wire containment comprising plastic or metal tubing. Access points for maintenance and inspection are required at certain intervals of length.
Trunking
An alternative form of containment to conduit, comprising U-shaped plastic or metal with a removable lid.
Meter tails (or, tails)
The single-core cables connected to the electricity meter. On the supply side these connect the meter to the line and neutral conductors of the supply cable, via the service head (or cut out) located on the end of the supply cable. On the consumer side these conductors are then joined to the distribution board, possibly through an isolator (as is becoming more common).
Singles
A cable consisting of a single conductor.
Multi-core
A cable consisting of two or more conductors (not counting any earth conductor).
Twin and earth (T&E)
A commonly used type of multi-core cable, characterised by its flat profile and grey-coloured polyvinyl chloride sheath. It contains three conductors, two of which are insulated (line and neutral), and it is from this that the name twin and earth derives.
Steel-wire armoured (SWA)
Steel wire protected cable, mandatory for outdoor or buried use unless equivalent protection is provided via containment.
Flex
Refers to the flexible cord of a portable appliance.

Voltage and phases

High voltage
Any voltage in excess of low voltage. This is usually found only in industrial processes and electricity transmission and distribution networks.
Low voltage
Exceeding extra-low voltage, but not exceeding 1000 volts AC RMS or 1500 volts DC between conductors, and not exceeding 600 volts AC RMS or 900 volts DC between conductors and Earth. Almost all domestic; light commercial (e.g., offices) and industrial (for three-phase machinery) power is low voltage for regulation purposes.
Extra-low voltage (ELV)
Not exceeding 50 volts AC RMS or 120 volts ripple-free DC.
Separated extra-low voltage (SELV)
Extra-low voltage system that is also electrically isolated.
Single phase, three phase
At low voltage electricity may be supplied by the distributor (DNO) as either single or three phase. A single phase supply will comprise a single line conductor and a neutral conductor. A three phase supply will comprise three line conductors each pair with a phase separation of 120 degrees and (optionally) a neutral conductor. A separate earth conductor will normally be supplied in both cases but may not be present depending on the connection type.

Earthing (bonding)

Bonding (including main bonding, supplementary bonding and equipotential bonding)
Connection made to Earth, for protective purposes, either for individual components, for other metal objects in the premises (such as gas, water, or oil piping), or for the installation (or some part of it) as a whole.
Earth/ground rod
A long rod placed into the ground, bonding, with low impedance, the installation to Earth potential. Usually made from copper-clad, galvanised or stainless steel or copper, for corrosion prevention. There are other types of Earth bonding, such as: an Earth plate, an Earth mesh, or an Earth ring.

Circuit terminology

Accessory
A switch, socket, ceiling rose, etc., forming part of an electrical installation.
Load
Something that requires and consumes electricity to function, e.g. a lightbulb, appliance, etc.
Circuit
A set of electrical wires and connections, forming part of an installation, between a distribution board and a fixed load, or between a distribution board and an accessory or daisy-chained set of accessories for connecting loads (sockets or light fittings), or between two distribution boards, enabling power to be provided. I.e. a final circuit or distribution circuit.
Distribution circuit
A circuit whereby one distribution board supplies power to another (via a protective device like a breaker).
Final circuit
A circuit providing power to a set of sockets, light fittings, or fixed equipment, from a single protective device (breaker) in a distribution board. (Not applicable to RCDs in a split way configuration which each sit behind a set of MCBs – each MCB would serve an individual final circuit in such a setup). Each final circuit will be arranged in a radial or ring final form if not simply serving a single fixed appliance. It may also have one or more fused or unfused spurs attached. The use of the word final comes from the fact that these circuits are the last piece of the power distribution infrastructure, finally delivering generated power to where it will be consumed.
Radial
A circuit where the conductors providing the power circuit (and earthing) are simply connected from one accessory (e.g. socket) to the next in a daisy-chain like fashion. You might think of this as the supplied power radiating out from the source to reach each accessory.
Ring (or ring final)
A ring final circuit is similar to a radial except what would be the end of the circuit instead loops back to the source protective device in the distribution board. Thus each individual conductor, line, neutral and earth, actually forms a loop (or ring), from the source, out, and back around to the source again. This has long been a standard means for wiring domestic and other light commercial premises in the UK, but is not often seen elsewhere in the world. It allows power between source and accessories to be split between two parallel paths. On the downside though it's more difficult to test, and should a break in a connection occur it could go unnoticed leading to one side of the ring potentially taking on an excessive amount of current flow, and increased earth fault loop impedance increasing disconnection times.
Loop
This term applies to radial lighting circuits where junctions are made at ceiling roses with line and switched line wires. Not to be confused with the loop-like arrangement of a ring final circuit.
(Unfused) spur
A branch off of a final circuit supplying a single accessory, especially from a ring final circuit.
Fused spur
A spur branched off of a final circuit via a connection protected by a suitable fuse, and thus one that may connect to more than one accessory.
A de-energized circuit
A circuit that is isolated from power and not at a potential different from Earth, and thus safe to work on.