Ring circuit

Electrical wiring technique

  • 9 min read
  • 6 chapters

Related on Lably

Through Electrical wiring, United Kingdom and Electrical network

Ring circuits are used in distribution for power and lighting. Rings at the final consumer current draw off point either for power or lighting are known as a ring final circuit. Ring final circuits are often termed by the historical name ring main in the United Kingdom.

Ring circuits are subject to typical cable protection relating for all types of circuit topologies, in which the cable is at a higher amperage loading than the protective device's (breaker) value.

In the United Kingdom there is an anomalous ring final circuit with the cable at a lower amperage loading than the protective device. It is under a waiver, 433.1.204 in British Standards 7671.

Ring final circuits in the United Kingdom splits ring circuits into two types:

  1. The 433.1.204 ring final having the cable at a lower maximum amperage rating than the protective device;
  2. Ring circuits having the cable at a higher maximum amperage rating than the protective device.

433.1.204 ring final in the UK

If a circuit designed with the cable at a lower maximum amperage loading than the protective device then 433.1.204 of BS 7671 is triggered. The standard states that such a circuit must only be a ring final - not a radial or star. The 433.1.204 implementation of the ring circuit is predominately used in the United Kingdom where it was developed, and to a lesser extent in countries that adopted the British electrical standards.

The 433.1.204 ring final waiver in BS 7671 simply says in layman's terms:

  1. The circuit must be a ring final (the two cable legs into the protective device double the circuits amperage rating over the cable's amperage rating);
  2. Protective device must be either 30A or 32A MCB/RCBO/AFDD/fuse;
  3. A minimum of 2.5mm2 cable used;
  4. The cable must have copper conductors;
  5. Minimum current capacity of the cable must be 20A, taking into account derating;
  6. If socket-outlets are to be installed on the ring final they must only be the BS 1363 socket-outlet accessory family - the Type G 13A square pin plug and socket.

Further guidance for 433.1.204 is in Appendix 15 of BS 7671, recommending such as: a maximum coverage of 100 square metre floor area and that the load must be reasonably distributed around the ring final.

A ring final when designed to the 433.1.204 of BS 7671 enables the use of smaller diameter cable than used in a radial circuit of equivalent total current capacity, giving economic installation. The reduced diameter conductors in the flexible cords connecting an appliance to the plug intended for use with sockets on a ring final circuit are individually protected by a fuse in the plug. Its prime advantages over radial circuits are a reduced quantity of cable used, lower voltage drop at the furthest point of the circuit, and greater flexibility of connected appliances and equipment.

Because both ends of the ring's cable are connected to the same protective device, current can travel in two directions around the ring to reach any given load. If the load is evenly split across the two directions, the current in each direction is half of the total load, allowing the use of cable with half the total current-carrying capacity. In practice, the load does not always split evenly.